WATERLESS WG2A Smart Logic Controller

WATERLESS-WG2A-Smart-Logic-Controller-product

Eolas Táirge

Sonraíochtaí

  • Model: Smart Logic Controller
  • Functions: PLC Functions & Sequences
  • Monaróir: Total Green Mfg.
  • Control: PLC controlled
  • Stage: 2-stage and multi-function units
  • Compatibility: Works with various heat/cool thermostats

Séanadh
Proper installation and servicing of the Total Green Mfg. Heat Pump is essential to its reliable performance. All Total Green Mfg. systems must be installed and serviced by a qualified HVAC contractor. Equipment sizing, selection and installation are the sole responsibility of the installing contractor.
Installations of equipment on an existing copper earth loop design that does not match a current Total Green Mfg. earth loop design is not permitted, will void all warranties on the equipment, and are the sole responsibility of the installing contractor. Installation must be made in accordance with the instructions set forth in this manual. Failure to provide installation by a qualified HVAC contractor in a manner consistent with this manual will void and nullify the limited warranty coverage for the system.
Total Green Mfg. shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of any field specified components.

All Total Green Mfg. 2 stage and multi-function units will have separate terminal strips labeled “thermostat/zone board” and “air handler/furnace” for low voltage agus atá faoi rialú PLC.
Chun go bhfeidhmeoidh an trealamh i gceart, ní mór an teirmeastat nó an bord crios a cheangal leis an stiall “críochfort teirmeastait/bord crios”. Ní mór an láimhseálaí aeir nó an foirnéis a cheangal leis an stiall chríochfoirt “láimhseálaí aeir/foirnéis”. Beidh stiallacha críochfoirt bhreise ann freisin le haghaidh feidhmeanna éagsúla bunaithe ar an gcineál samhail a bhfuil tú ag obair leis. Is chun forlíonadh a dhéanamh ar an lámhleabhar suiteála atá sainiúil do d’aonad atá an fhaisnéis a chuirtear ar fáil anseo.

TÁBHACHTACH: For WG2A, WG1AH, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

Rialaitheoir loighic cliste

WG2A Forced Air Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to
    “X”. During this 60 second time period, the compressor will only operate in 1st stage only giving the system a chance to recover before setting a hard lock out. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagAthshocraítear an glasáil má mhúchtar an t-aonad comhbhrúiteora agus má chuirtear ar ais ar an lasc é chomh fada agus nach bhfuil an lasc teochta urscaoilte oscailte. Tá cnaipe athshocraithe láimhe ag an lasc teochta urscaoilte. Beidh athshocrú láimhe ag teastáil i gcónaí i gcás lasc teochta urscaoilte oscailte, mar aon le toirt íseal.tagTimthriall cumhachta e. Tá na lasca brú uathoibríoch.
  2. A “Y1” call starts 1st stagtéamh nó fuarú a leanfaidh ar aghaidh ar feadh 20 nóiméad agus ansin am go dtí an 2ú soicindtagmá théann an t-am sin thart gan an teirmeastat ag glaoch “Y2”. Má tá an t-aonad i mód téimh, uair amháin ar feadh 2 soicindtagNuair a thosaíonn sé, cuirfidh lasc ama 20 nóiméad teas AUX ar siúl má théann an t-am sin thart gan an glao téimh a bheith sásaithe. Nuair a bheidh gach rud...tagMá glaodh orthu, fanfaidh siad glaoite go dtí go sásóidh an teirmeastat go hiomlán.
  3. If more than 3 consecutive “Y1” calls take place without the thermostat calling for 2nd staglaistigh de 20 nóiméad nó, roimh an 20 nóiméad den dara stagRitheann an lasc ama amach, ar an gceathrú glao “Y1”, cuirtear tús le timthriall cothabhála a choinneoidh agus a ghlasálfaidh an córas go dtí an 2ú soicind.tagar feadh 5 nóiméad chun a chinntiú go bhfillfidh an ola ar an gcomhbhrúiteoir. Má tá an córas criosaithe le haer, cuirfidh críochfort Sárú Crios “D” fuinneamh suas go 24 volta. Mar a thuairiscítear i lámhleabhar suiteála d’aonaid, is féidir an comhartha 24 volta seo a úsáid mar aon le hathsheachadán aonraithe a sholáthraítear ar an láthair chun glaoch ar an gcrios is mó a oscailt agus an crios sin a choinneáil.amposcailte ionas nach bhfeiceann an séidire brú statach ard le linn na 5 nóiméad sin. Glasálann an timthriall cothabhála aon ghlao eile go dtí go mbeidh sé críochnaithe. Tar éis an timthrialla cothabhála, nó má dhéantar glao “Y2” sula dtarlaíonn an timthriall cothabhála, athshocraíonn an cuntar ar ais go náid. Fágann sé seo go bhfuil ár gcóras cairdiúil don chrios mar go gceadaíonn sé fíor-2 soicind.tagtéamh agus fuarú.
  4. There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
  5. When the thermostat is set to cooling mode, the “O” signal energizes the reversing valve and locks out the aux heat output.
  6. In an effort the reduce energy consumption, the PLC turns power off to the crank case heater when the compressor runs.
  7. This PLC program also allows the use of almost any heat/cool thermostat. Even if a single stage heat/cool only thermostat is used, the PLC program will control all functions staging 2nd stage and AUX Heat as needed.

WGxAH Single and Two Stage Forced Air with Hydronic Heating Function

In addition to the function and features as described for WG2A units, The PLC program for the WGxAH units allows for switching priority call from forced air to hydronic heating as well as a feature
called “Split Zone” that are installer optioned by choosing jumper settings as described below.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating over hydronic heating. When this jumper is removed, hydronic heating becomes the priority call.
  • Split Zone is a feature which allows you the ability to heat one zone or floor with hydronic heat and another zone or floor with forced air. Split Zone is active by removing the priority call jumper across “R” and “AW” moving it across the “R” and “SZ” of the field wiring terminal block.
  • While in “Split Zone” mode, the compressor unit will provided forced air heating to the air zone. When the buffer storage tank calls for heat, the compressor unit will shift to heat water. Should a call for the air zone take place while the compressor unit is heating water, the call goes directly to the aux heat source to maintain the air zone. Once the tank temperature is satisfied, the system diverts back to normal air heating with the compressor unit.
  • When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • The Hydronic heating function is disabled anytime the “O’ terminal is energized placing the unit in cooling mode.

WG2AD Aer Éigeantach le Feidhm Téimh Uisce Baile

Chomh maith leis an bhfeidhm agus na gnéithe a bhfuil cur síos orthu d’aonaid WG2A mar a thuairiscítear sa chéad chuid den doiciméad seo, ceadaíonn clár PLC na n-aonad WG2AD glao tosaíochta a athrú ó aer fórsaithe go téamh uisce tí.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating/cooling over domestic water heating. When this jumper is removed, domestic water heating becomes the priority call.
  • When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • An added functional PLC feature exclusive to the WG2AD model which allows water heating up 120 degrees, is the unit’s ability to maintain compressor stability by throttling the compressor load as needed to control discharge pressure.

WG1H 100% Hydronic Heated and Chilled Water Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure, HX Low and Discharge temperature switches are made. An open safety switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagAthshocraítear an glasáil má mhúchtar an t-aonad comhbhrúiteora agus má chuirtear ar ais ar an lasc é chomh fada agus nach bhfuil an lasc teochta urscaoilte oscailte. Tá cnaipe athshocraithe láimhe ag an lasc teochta urscaoilte. Beidh athshocrú láimhe ag teastáil i gcónaí i gcás lasc teochta urscaoilte oscailte, mar aon le toirt íseal.tagtimthriall cumhachta e. Tá na lasca brú agus teocht íseal HX uathoibríoch.
  2. An “N” call starts the circulator pump for 30 seconds prior to the compressor to allow for full flow through the HX (heat exchanger) prior to starting the compressor. Once the call is complete, the pump will run an addition 30 seconds after the compressor stops to purge the HX of any residual heat. This occurs regardless of either a heated or chilled water call.

If you have any questions regarding any of these functions, please contact Total Green Mfg. at 419-678-2032 le haghaidh tacaíochta teicniúla.

Ceisteanna Coitianta

  • Q: How do I prioritize air heating over hydronic heating in WGxAH units?
    A: Remove the jumper between R and AW terminals on the field wiring terminal strip.
  • Q: How does Split Zone feature work in WGxAH units?
    A: Move the jumper from R and AW terminals to R and SZ on the field wiring terminal block to activate Split Zone.