KMC CSC-1001 Controllers

Tharview

CSC-1001 Constant Volume Controllers have been discontinued. However, they can be replaced with a CSC-2001/2003/3011 controller and (for VAV applications) an RCC-1008/1108 relay.
For more information about a particular device, see the respective device data sheet, installation guide, and/or application guide.
Tharview

Fógraí Tábhachtacha

Is chun críocha faisnéise amháin atá an t-ábhar sa doiciméad seo. Féadfaidh an t-ábhar agus an táirge a ndéanann sé cur síos air a athrú gan fógra. Ní dhéanann KMC Controls, Inc. aon uiríoll nó barántas maidir leis an doiciméad seo. Ní bheidh KMC Controls, Inc. faoi dhliteanas ar chor ar bith i leith aon damáiste, díreach nó teagmhasach, a eascraíonn as nó a bhaineann le húsáid an doiciméid seo.

CSC-1001 Function

The CSC-1001 is designed for use with normally open dampers in either of the following applications:

  • Constant air volume (CAV) terminals
  • Variable air volume (VAV) terminals with maxi-mum flow limiting

CAV operation is configured by connecting a nor-mally open actuator to the C port on the controller (or the H port if the T port is open) and adjusting the setpoint screw to the desired flow setpoint. Airflow is measured by an SSS-1000 series sensor connected between the Hl and LO ports. Adjusting the setpoint screw clockwise will increase the flow setpoint; adjusting the screw counter-clockwise will decrease the flow setpoint. The T port may be exhausted to atmosphere during constant volume operation.

When used in VAV applications where a high flow limit is necessary, the controller should have a normally open damper connected to the H port, a reverse acting thermostat connected to the T port, and an SSS-1000 series flow pickup between Hl and LO. The C port should be capped (as installed from the factory). With the T port exhausted, or at a low pressure, the setpoint screw can be adjusted for the maximum flow limit. The controller will supply the H port with the higher of either the thermostat signal or the configured maximum flow limit pressure, thus limiting the maximum airflow once the thermostat signal falls below the maximum flow setpoint.

Sample hIarratais

Constant Volume Airflow adjusted using the LO Adjustment Knob (center knob).
Sample hIarratais

High Flow adjusted using the LO Adjustment Knob (center knob)
Sample hIarratais

NÓTA: On the CSC-3011, ensure the Damper Action Selection Dial is set properly (Normally Open in these examples).

Replacement by CSC-2001/2003

CSC-2000 Series Reset Volume Controllers may be used to obtain the same functionality of CSC-1001 Constant Volume Controllers. For constant volume applications, a CSC-2001/2003 should be used in conjunction with a normally open actuator (connect-ed to the B port) and an SSS-1000 series flow pickup (connected between X and Y). The T port should be exhausted. The LO adjustment knob (center knob on the front) may be set to maintain the desired constant volume airflow. (See the Constant Volume Applica-tion illustration on the previous page.)

VAV applications requiring a high limit can be re-placed with a CSC-2001/2003 and an RCC-1008/1108 High Selector Relay. The normally open actuator should be connected to the B port of the RCC. The S1 and S2 ports of the RCC should be supplied from the B ports of the CSC-2001/2003 and a reverse acting thermostat. The high flow limit can be adjusted us-ing the LO adjustment knob on the CSC-2001/2003. An SSS-1000 series flow pickup should be connected between the X and Y ports of the CSC-2001/2003, and the T port should be exhausted. (See the VAV Application with a High Flow Limit illustration on the previous page.)

For CSC-2001/2003 adjustment and other information, see the CSC-2000 series Application Guide.
Cód QR

Replacement by CSC-3011

A CSC-3011 “universal” Reset Volume Controller may also be used to obtain the same functionality of CSC-1001 Constant Volume Controllers. For constant volume applications, a CSC-3011 should be used in conjunction with a normally open actuator (connect-ed to the B port) and an SSS-1000 series flow pickup (connected between H and L). The T port should be exhausted. The LO Stat (“low thermostat differential pressure”) adjustment knob (center knob) may be set to maintain the desired constant volume airflow. (See the Constant Volume Application illustration on the previous page.)

Cinntigh an Damper Action Selection Dial is set properly (Normally Open in these examples).

VAV applications requiring a high limit should be replaced with a CSC-3011 and an RCC-1008/1108 High Selector Relay. The normally open actuator should be connected to the B port of the RCC. The S1 and S2 ports of the RCC should be supplied from the B ports of the CSC-3011 and a reverse acting thermostat. The high flow limit can be adjusted using the LO Stat adjustment knob on the CSC-3011. An SSS-1000 series flow pickup should be connected be-tween the H and L ports of the CSC-3011, and the T port should be exhausted. (See the VAV Application with a High Flow Limit illustration on the previous page.)

For CSC-3011 adjustment and other information, see the CSC-3000 series Application Guide.
Cód QR

Is mór againn d'Aiseolas!
Cabhraigh linn an doiciméad seo a fheabhsú.
Cliceáil anseo chun suirbhé 3 nóiméad a dhéanamh.
Cuidíonn do chuid ionchuir linn ár ndoiciméid a dhéanamh níos soiléire agus níos úsáidí.

Rialuithe KMC, Inc.
19476 Tiomántán Tionsclaíoch
Páras Nua, IN 46553
574.831.5250
www.kmccontrols.com
eolas@kmccontrols.com

Lógó KMC

Doiciméid / Acmhainní

KMC CSC-1001 Controllers [pdfTreoir Úsáideora
CSC-2001, CSC-2003, CSC-3011, CSC-1001 Controllers, CSC-1001, Controllers