  • Tá suiteáil agus seirbhísiú ceart Caidéal Teasa Total Green Mfg. riachtanach chun a fheidhmíocht iontaofa a chinntiú. Ní mór do chonraitheoir HVAC cáilithe gach córas Total Green Mfg. a shuiteáil agus a sheirbhísiú. Is ar an gconraitheoir suiteála amháin atá an fhreagracht maidir le méid, roghnú agus suiteáil an trealaimh.
  • Ní cheadaítear trealamh a shuiteáil ar dhearadh lúb cré copair atá ann cheana féin nach bhfuil ag teacht le dearadh lúb cré reatha Total Green Mfg., cuirfidh sé sin gach barántas ar an trealamh ar neamhní, agus is é an conraitheoir suiteála amháin atá freagrach as. Ní mór an tsuiteáil a dhéanamh de réir na dtreoracha atá leagtha amach sa lámhleabhar seo. Má mhainnítear suiteáil a sholáthar ag conraitheoir HVAC cáilithe ar bhealach atá comhsheasmhach leis an lámhleabhar seo, cuirfear neamhní ar an gclúdach barántais theoranta don chóras.
  • Ní bheidh Total Green Mfg. faoi dhliteanas as aon locht, feidhmíocht mhíshásúil, damáiste nó caillteanas, bíodh sé díreach nó iarmhartach, a bhaineann le dearadh, monarú, tógáil, cur i bhfeidhm nó suiteáil aon chomhpháirteanna sonraithe sa réimse.
  • All Total Green Mfg. forced air units will have separate terminal strips labeled  “thermostat/zone board” and “air handler/furnace” for low voltage and are PLC  “controlled.
  • For proper equipment function, the thermostat or zone board must be tied to the  “thermostat/zone board terminal” strip. The air handler or furnace must be tied to the “air handler/furnace” terminal strip. There will also be additional terminal strips  for various functions based on the model type you may be working with. The information provided here is to supplement the installation manual specific to your unit.
  • IMPORTANT: For WGxA, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

WG1A Aer Éigeantach Amháin – Liosta feidhmeanna

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to  “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagAthshocraítear an glasáil má mhúchtar an t-aonad comhbhrúiteora agus má chuirtear ar ais ar an lasc é chomh fada agus nach bhfuil an lasc teochta urscaoilte oscailte. Tá cnaipe athshocraithe láimhe ag an lasc teochta urscaoilte. Beidh athshocrú láimhe ag teastáil i gcónaí i gcás lasc teochta urscaoilte oscailte, mar aon le toirt íseal.tagTimthriall cumhachta e. Tá na lasca brú uathoibríoch.
  2. A “Y” call starts heating or cooling. A 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once aux. heat is called, aux. heat will stay called until the thermostat fully satisfies.
  3. Tá geansaí suiteáilte ar bhloc críochfoirt sreangaithe allamuigh atá marcáilte “A” agus “S”. Agus an geansaí suiteáilte, feidhmeoidh an t-aonad le stiall teasa chúnta mar is gnách. Má bhaintear an geansaí, téann an PLC i mód dé-bhreosla ag stopadh an chomhbhrúiteora nuair a bhíonn glao ann ar théamh cúnta. Nuair a bheidh an glao teasa cúnta críochnaithe, cuireann lasc ama fuaraithe 5 nóiméad cosc ​​ar an gcomhbhrúiteoir atosú ar ghlao “Y” go dtí go mbeidh an t-am caite. Tugann sé seo am don fhoirnéis fuarú ionas nach mbíonn brú urscaoilte ard nó glasáil mar thoradh ar aer te nuair a atosóidh an comhbhrúiteoir.
  4. Nuair a bhíonn an teirmeastat socraithe go mód fuaraithe, cuireann an comhartha “O” fuinneamh ar an gcomhla aisiompaithe agus glasálann sé aschur an teasa chúnta.
  5. D’fhonn an tomhaltas fuinnimh a laghdú, múchann an PLC cumhacht an téitheoir cás an chromáin nuair a bhíonn an comhbhrúiteoir ag rith.
  6. This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
  7. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

WG2A Aer Éigeantach Amháin – Liosta feidhmeanna

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to“X”. During this 60 second time period, the compressor will only operate in 1st stagag tabhairt deis don chóras téarnamh sula socraítear glasáil chrua. Tá sé seo chun glaonna núiseacha a chosc, go háirithe ag tús an tséasúir fuaraithe nuair a bhíonn na Lúba Talún ag a bhfuar is mó. Socraítear “X” le haon choinníoll glasála crua. Ag casadh an toirt ísealtagAthshocraítear an glasáil má mhúchtar an t-aonad comhbhrúiteora agus má chuirtear ar ais ar an lasc é chomh fada agus nach bhfuil an lasc teochta urscaoilte oscailte. Tá cnaipe athshocraithe láimhe ag an lasc teochta urscaoilte. Beidh athshocrú láimhe ag teastáil i gcónaí i gcás lasc teochta urscaoilte oscailte, mar aon le toirt íseal.tagTimthriall cumhachta e. Tá na lasca brú uathoibríoch.
  2. Tosaíonn glao “Y1” ar an 1ú stagtéamh nó fuarú a leanfaidh ar aghaidh ar feadh 20 nóiméad agus ansin am go dtí an 2ú soicindtagmá théann an t-am sin thart gan an teirmeastat ag glaoch “Y2”. Má tá an t-aonad i mód téimh, uair amháin ar feadh 2 soicindtage starts, a 20-minute timer will bring on AUX heat  should that time elapse without having satisfied the heating call. Once all stagMá glaodh orthu, fanfaidh siad glaoite go dtí go sásóidh an teirmeastat go hiomlán.
  3.  Má tharlaíonn níos mó ná 3 ghlao “Y1” as a chéile gan an teirmeastat ag glaoch ar feadh an 2ú soicindtaglaistigh de 20 nóiméad nó, roimh an 20 nóiméad den dara stagRitheann an lasc ama amach, ar an gceathrú glao “Y1”, cuirtear tús le timthriall cothabhála a choinneoidh agus a ghlasálfaidh an córas go dtí an 2ú soicind.tage   for 5 minutes to assure oil return to the compressor. If the system is air zoned, a Zone Override terminal “D” will energize to 24 volts. As described in your unit installation manual, this 24-volt signal can be used along with a field supplied isolation relay to call open the  largest zone and hold that damper open so the blower doesn’t see high static pressure during those 5 minutes. The maintenance cycle locks any other call out until completion. After the maintenance cycle, or if a “Y2” call is made before the maintenance cycle occurs, the
  4.  counter resets back to zero. This makes our system zone friendly as it allows for true 2 stagtéamh agus fuarú.
    There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a
    call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
  5.  Nuair a bhíonn an teirmeastat socraithe go mód fuaraithe, cuireann an comhartha “O” fuinneamh ar an gcomhla aisiompaithe agus glasálann sé aschur an teasa chúnta.
  6. D’fhonn an tomhaltas fuinnimh a laghdú, múchann an PLC cumhacht an téitheoir cás an chromáin nuair a bhíonn an comhbhrúiteoir ag rith.
  7.  This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
  8. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

Aer Éigeantach WG2AH le Feidhm Téimh Hidreonach

In addition to the function and features as described for WG2A units, The PLC program for the WG2AH units allows for switching priority call from forced air to hydronic heating as well as a  feature called “Split Zone” that are installer optioned by choosing jumper settings as described  below.

  1. Úsáidtear geansaí ar an stiall críochfoirt sreangaithe allamuigh idir na críochfoirt “R” agus “AW” chun tosaíocht a thabhairt don téamh aeir thar an téamh hiodrónach. Nuair a bhaintear an geansaí seo, is é an téamh hiodrónach an glao tosaíochta.
  2. Is gné í an Chrios Scoilte a ligeann duit crios nó urlár amháin a théamh le teas hidreonach agus crios nó urlár eile le haer fórsaithe. Gníomhaítear an Crios Scoilte tríd an geansaí glao tosaíochta a bhaint trasna “R” agus “AW” agus é a bhogadh trasna “R” agus “SZ” an bhloc críochfoirt sreangaithe allamuigh.
  3. Agus é i mód “Crios Scoilte”, cuirfidh an t-aonad comhbhrúiteora téamh aeir éigeantach ar fáil don chrios aeir. Nuair a iarrann an umar stórála maolánach teas, aistreoidh an t-aonad comhbhrúiteora chun uisce a théamh. Má tharlaíonn glao don chrios aeir agus an t-aonad comhbhrúiteora ag téamh uisce, téann an glao go díreach chuig an bhfoinse teasa chúnta chun an crios aeir a choinneáil. Nuair a bhíonn teocht an umair sásta, atreoraíonn an córas ar ais go gnáththéamh aeir leis an aonad comhbhrúiteora.
    1. When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, tosaíonn na caidéil uisce ag bunú sreabhadh maith uisce. 30 soicind ina dhiaidh sin stage, tosaíonn an comhbhrúiteoir. Nuair a bhíonn teirmeastat an umair sásta, stopann an comhbhrúiteoir agus leanfaidh an caidéal ag rith ar feadh 30 soicind sula múchtar é chun aon teas iarmharach a fháil ón malartóir teasa. Nóiméad amháin tar éis don chomhbhrúiteoir stopadh, dífhuinnítear an comhla 1-bhealach. Nóiméad amháin ina dhiaidh sin, is féidir leis an gcomhbhrúiteoir atosú le haghaidh glao crios aeir. Laghdaíonn na timthriallta uainithe seo caitheamh chomhpháirteanna an chórais trí gan a bheith orthu aistriú faoi bhrú ná ualach.
  4. Díchumasaítear an fheidhm téimh hiodróinigh aon uair a bhíonn an críochfort “O’ fuinnithe agus cuireann sé sin an t-aonad i mód fuaraithe.
  5. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

WG2AD Aer Éigeantach le Feidhm Téimh Uisce Baile

Chomh maith leis an bhfeidhm agus na gnéithe a bhfuil cur síos orthu d’aonaid WG2A mar a thuairiscítear sa chéad chuid den doiciméad seo, ceadaíonn clár PLC na n-aonad WG2AD glao tosaíochta a athrú ó aer fórsaithe go téamh uisce tí.

  • Úsáidtear geansaí ar an stiall críochfoirt sreangaithe allamuigh idir na críochfoirt “R” agus “AW” chun tosaíocht a thabhairt do théamh/fhuarú aeir thar théamh uisce tí. Nuair a bhaintear an geansaí seo, is é téamh uisce tí an glao tosaíochta.
  • When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, tosaíonn na caidéil uisce ag bunú sreabhadh maith uisce. 30 soicind ina dhiaidh sin stage, tosaíonn an comhbhrúiteoir. Nuair a bhíonn teirmeastat an umair sásta, stopann an comhbhrúiteoir agus leanfaidh an caidéal ag rith ar feadh 30 soicind sula múchtar é chun aon teas iarmharach a fháil ón malartóir teasa. Nóiméad amháin tar éis don chomhbhrúiteoir stopadh, dífhuinnítear an comhla 1-bhealach. Nóiméad amháin ina dhiaidh sin, is féidir leis an gcomhbhrúiteoir atosú le haghaidh glao crios aeir. Laghdaíonn na timthriallta uainithe seo caitheamh chomhpháirteanna an chórais trí gan a bheith orthu aistriú faoi bhrú ná ualach.
  • Gné bhreise feidhmiúil PLC atá eisiach don mhúnla WG2AD a ligeann don uisce téamh suas le 120 céim, is ea cumas an aonaid cobhsaíocht an chomhbhrúiteora a choinneáil tríd an ualach comhbhrúiteora a thréigean de réir mar is gá chun brú urscaoilte a rialú.
  • If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a  refrigerant leak.

Rialaitheoir loighic cliste
WG1H Uisce Téite agus Fuaraithe 100% Hiodróineach Amháin – Liosta feidhmeanna

  1. Seiceálann an PLC go bhfuil na lasca brú ÍSEAL/ARD, HX Íseal agus teocht urscaoilte déanta. Bíonn moill 60 soicind ag ionchur lasc sábháilteachta oscailte sula socraítear comhartha glasála agus locht go “X”. Tá sé seo chun glaonna núis a chosc, go háirithe ag tús an tséasúir fuaraithe nuair a bhíonn na Lúba Talún ag a bhfuar is mó. Socraítear “X” le haon choinníoll glasála crua. Ag casadh an toirt ísealtagAthshocraítear an glasáil má mhúchtar an t-aonad comhbhrúiteora agus má chuirtear ar ais ar an lasc é chomh fada agus nach bhfuil an lasc teochta urscaoilte oscailte. Tá cnaipe athshocraithe láimhe ag an lasc teochta urscaoilte. Beidh athshocrú láimhe ag teastáil i gcónaí i gcás lasc teochta urscaoilte oscailte, mar aon le toirt íseal.tagtimthriall cumhachta e. Tá na lasca brú agus teocht íseal HX uathoibríoch.
  2. Tosaíonn glao “N” an caidéal imshruthaitheora ar feadh 30 soicind roimh an gcomhbhrúiteoir chun ligean do shreabhadh iomlán tríd an HX (malartóir teasa) sula dtosaíonn an comhbhrúiteoir. Nuair a bheidh an glao críochnaithe, rithfidh an caidéal ar feadh 30 soicind breise tar éis don chomhbhrúiteoir stopadh chun aon teas iarmharach a ghlanadh ón HX. Tarlaíonn sé seo beag beann ar ghlao uisce téite nó fuaraithe.
  3. If the compressor unit sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor. The “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

Má tá aon cheist agat maidir le haon cheann de na feidhmeanna seo, déan teagmháil le Total Green Mfg. ag 419-678-2032 le haghaidh tacaíochta teicniúla.

Ceisteanna Coitianta

  • C: An féidir liom aon teirmeastat a úsáid leis an Rialaitheoir Lógic Chliste?
    A: Yes, the PLC program allows for the use of almost any heat/cool thermostat, but Total Green Mfg. recommends using  Honeywell 8000 series thermostats for optimal performance.